Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Allen-Bradley / Rockwell Automation |
| Product Series | Bulletin 1492 |
| Product Type | Fused Analog Interface / Termination Module |
| Catalog Number | 1492-TAIFM16-F-3 |
| Lifecycle Status | Active |
| Application | SIL 2 Safety Shutdown System |
| Compatible PLC Modules | Two 1756-IF16 Analog Input Modules |
| Number of Channels | 16 SIL 2 sensors or 32 standard sensors (DIP-switch selectable) |
| Fuse Protection | 32 fuse holders |
| Fuse Indication | Individual blown-fuse LED indicators |
| Input Signal | 4–20 mA or 0–5 VDC |
| Supported Signal Mode | Analog, single-ended voltage mode |
| Operating Voltage | 19.2–26.4 VDC |
| Maximum Current per Circuit | 0.25 A |
| Maximum Current per Module | 1 A |
| Reference Test Control Voltage | 19.2–30 VDC |
| Reference Test Control Current | 10 mA |
| Module Power Consumption | 0.5 W at 24 VDC |
| Blown-Fuse Indicator Current | 2 mA nominal |
| Maximum Recurring Peak Voltage | 100 Vp |
| Connection Interface | 25-pin D-shell connector |
| Mounting | DIN rail |
| Operating Temperature | 0–60°C |
| Operating Humidity | 5–95%, non-condensing |
| Dimensions (W × H × D) | 251 × 83 × 69.5 mm |
| Approx. Shipping Weight | 0.59 kg |
| Country of Origin | USA (manufacturing origin may vary; verify nameplate) |
| Certifications | cULus, CE |
FAQ
FAQ
Q1: What is the Allen-Bradley 1492-TAIFM16-F-3?
A: It is a fused analog interface module designed for ControlLogix SIL 2 safety shutdown applications.
Q2: Which PLC modules are compatible with it?
A: It is specifically designed to interface with two Allen-Bradley 1756-IF16 analog input modules.
Q3: How many sensors can it support?
A: It supports 16 SIL 2 sensors or up to 32 standard sensors, selectable through DIP switches.
Q4: Does this module have fuse protection?
A: Yes. It has 32 fuse holders with individual LED indicators to identify blown fuses.
Q5: What input signals does it support?
A: It supports 4–20 mA current-loop signals and 0–5 VDC signals. A 0–10 V signal should not be used because it may damage the interface module.
Q6: What is the operating voltage?
A: Its normal operating voltage range is 19.2–26.4 VDC.
Q7: What is the main safety application?
A: It is designed for SIL 2 safety shutdown systems, providing fused signal termination and interfacing for redundant analog input modules.
Q8: What are the dimensions and weight?
A: The module measures approximately 251 × 83 × 69.5 mm and has an approximate shipping weight of 0.59 kg. Actual packaged weight may vary.