Honeywell 8C-SDOX01 51307051-175 Series 8 Controller Digital Output Relay Extension  Module
Honeywell 8C-SDOX01 51307051-175 Series 8 Controller Digital Output Relay Extension  Module
Honeywell 8C-SDOX01 51307051-175 Series 8 Controller Digital Output Relay Extension  Module
Honeywell 8C-SDOX01 51307051-175 Series 8 Controller Digital Output Relay Extension  Module
Company Information
E-mail [email protected]
Mobile +8613950166376
Whatsapp +8613950166376
WeChat 13950166376

Manufacturer:Honeywell

Product Number:8C-SDOX01 51307051-175

Product Type:Digital Output Relay Extension Module

Origin:USA

Dimensions:61 x 153 x 145 mm

Weight:0.3 kg


FAQ
Click to rate this post!
[Total: 0 Average: 0]

Frequently Asked Questions (FAQ)

Q1: What type of output does the 8C-SDOX01 support?
A1: It provides 32 Form-C (SPDT) isolated dry contacts, suitable for both NO and NC configurations.

Q2: What is the maximum current per output channel?
A2: Up to 5A at 125/250VAC (resistive) or 3A at 30VDC (resistive).

Q3: Does the module provide isolation between channels?
A3: Yes, 1500VAC RMS or ±1500VDC isolation is provided between channels and to logic common.

Q4: What is the minimum load requirement?
A4: 5VDC and 10mA if never used for high loads; otherwise 100mA is required.

Q5: Is hot-swapping supported?
A5: Yes, the module can be inserted or removed under power.

Q6: What is the operating voltage for the module?
A6: It operates at 24VDC.

Q7: What is the electrical contact life?
A7: At 3A resistive load, the relay contact life is ≥100,000 operations.

Q8: Is this module compatible with redundant configurations?
A8: Yes, it works with DO modules like 8C-PDODA1 and IOTAs for redundant output extension.