Manufacturer:Honeywell
Product Number:RM7800L1053
Product Type:Burner Control
Origin:USA
Dimensions:127 x 127 x 133 mm
Weight:0.7 kg
FAQ
FAQ
Q1: What is the operating voltage of the Honeywell RM7800L1053?
A1: The operating voltage is 120 VAC with a tolerance of +10% to -15%, at 50 or 60 Hz.
Q2: What are the ambient temperature limits for operation?
A2: The RM7800L1053 can operate in environments from -40°C to 60°C.
Q3: Is the RM7800L1053 SIL rated?
A3: Yes, it is SIL 3 capable when used with dynamic self-check or AMPLI-CHECK™ flame amplifiers in a properly designed safety instrumented system.
Q4: Does this model support communication interfaces?
A4: Yes, it can communicate via an optional Modbus™ module.
Q5: What is the flame failure response time?
A5: The flame failure response time ranges from 0.8 to 3.0 seconds, depending on the selected flame amplifier.
Q6: What are the physical dimensions and weight of the RM7800L1053?
A6: The dimensions are 127 x 127 x 133 mm, and the weight is approximately 0.7 kg.
Q7: Can the RM7800L1053 be used in high humidity environments?
A7: Yes, it is rated for 85% RH continuous, non-condensing.
Q8: Which certifications does this product carry?
A8: It is approved by UL, CSA, FM, IRI, and complies with FCC Part 15 Class A emissions.