Manufacturer:Yokogawa
Product Number:ASI533-H00
Product Type:Analog Output Module
Origin:Japan
Dimensions:107.5 × 130 × 32.8 mm
Weight:0.3 kg
FAQ
FAQ
-
What is the maximum current output per channel of the ASI533-H00?
Each channel can output up to 23 mA, while standard operation is 4–20 mA. -
Are the analog output channels isolated?
Yes, all eight channels are fully isolated to prevent signal interference. -
What is the typical response time for output changes?
The step response time is 100 ms. -
What is the operating temperature range for this module?
The module operates reliably from -10°C to 55°C. -
Can the ASI533-H00 handle HART communication signals?
Yes, HART communication is supported for integration with control systems. -
What is the allowable load resistance for each output channel?
Up to 750 Ω at 20 mA and 600 Ω at 23 mA. -
Is the module suitable for panel or DIN rail mounting?
Yes, it supports both DIN rail and panel mounting options. -
What is the accuracy of the analog output signals?
The output accuracy is ±48 µA.